D297 Smoke detector, long-range beam, 12V

Commercial Type No.: D297
Product No.: 4.998.140.350

D297 Smoke detector, long-range beam, 12V
  • Details
    Alarm Current (Receiver) 75 mA at 12 VDC
    Standby Current Receiver: 50 mA at 12 VDCTransmitter: 20 mA at 12 VDC
    Operating Voltage 10.2 VDC to 15.0 VDC
    Alarm contacts Normally Open (N/O) contacts rated 1 A, 60 VDC maximum for DC resistive loads, do not use with capacitive or inductive loads
    Auxiliary alarm contacts Normally Open (N/O) contacts rated 1 A, 60 VDC maximum for DC resistive loads, do not use with capacitive or inductive loads
    Trouble contacts Normally Closed (N/C) contacts rated 1 A, 60 VDC maximum for DC resistive loads, do not use with capacitive or inductive loads
    Environment Indoor, dry
    Relative humidity 0% to 95%, non‑condensing
    Temperature(storage and operating) -22°F to +130°F (-30°C to +54°C) For UL Listed installations, the range is +32°F to +130°F (0°C to +54°C)
    Dimensions 7 in. x 5.5 in. x 5.5 in. (17.8 cm x 14 cm x 14 cm)
    Mounting Mount to 3.5 in. or 4-in. square or octagonal electrical boxes or European Beza boxes
    Adjustability Internally adjustable optics for ±90° horizontal, and ±10° vertical adjustment
    Sensitivity Field selectable for 20%, 30%, 40%, 50%, 60%, or 70% beam obscuration
    System Signaling Conventional four-wire system, do not use with systems incorporating an alarm verification feature
    Signal Delay Fire: Selectable 30 sec or 5 secTrouble: 20 ± 2 sec
    Spacing(distance between systems) 60 ft. (18 m) maximum, spacing confirmed by Underwriters Laboratories (UL) testing
    Transmission range 30 ft. (9 m) to 350 ft. (107 m)
    Tamper Receiver: Access door tamper switch in series with trouble contacts. Transmitter: When the cover is removed, the cover tamper switch interrupts transmission

    Images

     
  • Certificates (3)
    Title Type Language
    FM PDF
    CSFM PDF
    HKFSD PDF
     
  • Documents (2)
    Title Type Language
    Data Sheet PDF
    Installation Manual PDF
     
 

Accessories

D344-RL Remote indicator plate

D344-RL Remote indicator plate

Used with the D340 Series Duct Smoke Detector Housings

Commercial Type No.: D344-RL
Product No.: 4.998.140.354

 
D344-RT Remote test/indicator plate, 24V

D344-RT Remote test/indicator plate, 24V

Use with a D340/D341/D342 or D343 (legacy product) Duct smoke housing or D296/D297 Long‑range beam smoke detector.

Commercial Type No.: D344-RT
Product No.: F.01U.024.868

 
 
D308 Field test kit for D296/D297

D308 Field test kit for D296/D297

Allows testing the calibration of the D296 and D297 beam smoke detectors

Commercial Type No.: D308
Product No.: 4.998.137.953